Modeling and Analysis of Asymmetrical Faults for Relay Settings in Electric Power Protection System Learning

12 Halaman

Penulis

, , , ,

ISSN

2686-1208

Penerbit

BIAR Publisher

Diterbitkan pada

08/09/2022

Bahasa

English

Kata Kunci

, , ,

Abstrak

This study examines the analysis of asymmetrical faults, namely single-phase ground faults, for e-jobsheet products based on Information and Communication Technology (ICT) or utilizing computer programs for study. A study of short-circuit faults in the electric power system is used to solve problems in the field of reliability and protection. The electric power system involves handling single-phase short-circuit faults to ground, which, if not neutralized, can cause equipment damage to the electric power system. Parameters from the modeling and analysis of asymmetrical faults are used for setting the Ground Fault Relay, often known as the Ground Fault Relay (GFR). The research study begins with modeling the interconnection system in the form of a reactance diagram, then modeling it with the bus impedance matrix equation to determine the magnitude of the short-circuit impedance value on the diagonal matrix. Next, the fault current of a single-phase short circuit to ground is calculated. Based on these results, the amount of the relay setting is determined. The results showed that the asymmetrical fault current was 3.0 Pu, with a setting time value of 2.45 seconds. The results of the study are used for learning relay settings. The simulation program was validated by experts, receiving a very good category with an Aikensv index of 0.872.